No.3286 Gongnong Street,
Changchun,
China |
0086-431-85694042 ........
0086-431-85680541 |
0086-431-85683672 |
130021 |
|
|
|
| |
| HEAT SHRINKABLE
CONDUCTIVE BREAKOUT |
| |
 |
|
| Description
|
| |
CIAC ® HCB Breakouts
are designed for the conductive screening and
sealing of cable crutches and provide resistance
to abrasion, weathering and chemical attack. Extensively
tested and widely used both these products have
been proven through many years service in the
field. The breakout can be used in cable terminations
up to 42KV
- Minimum shrink temperature: 110 ¡æ
- Minimum fully recovered temperature: 130 ¡æ
|
|
|
| |
| Dimensions |
Core |
Voltage
Grade |
Cross
Section(mm2) |
Main
Daimeter |
Finger
Diameter |
Recovered
Length |
Recovered
Wall |
Supplied |
Recovered |
Supplied |
Recovered |
Full |
Finger |
Main |
Finger |
2 |
1KV |
4-16 |
25 |
12 |
10 |
3.5 |
86 |
30 |
2.0 |
1.4 |
2 |
1KV |
25-50 |
40 |
18 |
15 |
5.6 |
120 |
40 |
2.5 |
2.2 |
2 |
1KV |
70-120 |
50 |
22 |
20 |
8.7 |
145 |
50 |
2.5 |
1.8 |
2 |
1KV |
150-240 |
75 |
36 |
30 |
11 |
155 |
55 |
2.6 |
2.8 |
3 |
1KV |
4-6 |
30 |
14 |
10 |
3.5 |
120 |
40 |
2.5 |
1.8 |
3 |
1KV |
10-16 |
40 |
18 |
15 |
5.6 |
120 |
40 |
3.0 |
2.0 |
3 |
1KV |
25-50 |
50 |
24 |
25 |
6.8 |
160 |
60 |
3.5 |
2.3 |
3 |
1KV |
70-120 |
65 |
30 |
28 |
8.9 |
200 |
60 |
3.5 |
3.0 |
3 |
1KV |
150-240 |
75 |
36 |
30 |
9 |
200 |
60 |
4.0 |
3.0 |
3 |
10KV |
25-50 |
75 |
36 |
30 |
9 |
200 |
60 |
4.0 |
3.0 |
3 |
10KV |
70-120 |
90 |
45 |
38 |
14 |
200 |
60 |
4.0 |
3.0 |
3 |
10KV |
150-240 |
110 |
55 |
58 |
19 |
200 |
60 |
4.0 |
3.5 |
3 |
10KV |
300-400 |
140 |
68 |
60 |
25 |
235 |
75 |
4.0 |
3.0 |
3 |
36KV |
25-50 |
110 |
55 |
58 |
19 |
200 |
60 |
4.0 |
3.5 |
3 |
36KV |
70-120 |
140 |
68 |
60 |
25 |
235 |
75 |
4.0 |
3.0 |
3 |
36KV |
150-240 |
160 |
79 |
65 |
27 |
220 |
70 |
4.5 |
3.5 |
3 |
36KV |
300-400 |
200 |
90 |
70 |
30 |
263 |
70 |
4.5 |
4.2 |
| |
4 |
1KV |
4-6 |
32 |
15 |
10 |
3.5 |
120 |
45 |
2.5 |
1.8 |
4 |
1KV |
10-16 |
42 |
20 |
15 |
6.4 |
127 |
42 |
2.5 |
1.1 |
4 |
1KV |
25-50 |
56 |
26 |
22 |
7 |
180 |
60 |
3.0 |
2.7 |
4 |
1KV |
70-120 |
68 |
34 |
28 |
9 |
200 |
70 |
3.0 |
3.0 |
4 |
1KV |
150-240 |
80 |
42 |
32 |
11 |
200 |
70 |
3.5 |
3.0 |
4 |
1KV |
300-400 |
90 |
46 |
36 |
14 |
200 |
70 |
4.0 |
3.0 |
| |
5 |
1KV |
4-6 |
45 |
22 |
10 |
3.5 |
160 |
50 |
2.5 |
1.8 |
5 |
1KV |
10-16 |
45 |
22 |
10 |
3.5 |
160 |
50 |
2.5 |
1.8 |
5 |
1KV |
25-50 |
66 |
33 |
21 |
7 |
180 |
60 |
3.0 |
2.5 |
5 |
1KV |
70-120 |
75 |
38 |
25 |
9 |
200 |
70 |
3.0 |
2.5 |
5 |
1KV |
150-240 |
100 |
50 |
36 |
12 |
205 |
70 |
3.0 |
2.5 |
5 |
1KV |
300-400 |
120 |
60 |
38 |
15 |
220 |
80 |
3.5 |
3.0 |
|
| |
| Note: |
- Standard Color: Black
- Adhesive linings available subject to factory quotation
|
| |
| Technical Data |
| Property |
Test Method |
Typical Data |
| Operating temperature |
IEC216 |
-55 to +105 ¡æ |
| Tensile Strength |
ASTM D 2671 |
10MPa min. |
| Tensile Strength after thermal aging(136
¡æ /168hrs) |
ASTM D 2671 |
7MPa min. |
| Elongation at break |
ASTM D 2672 |
300% min. |
| Elongation at break after thermal aging(136
¡æ /168hrs) |
ASTM D 2673 |
210% min. |
| Water absorption |
ISO62 |
1% max. |
| Volume resistance |
IEC93 |
10 4 ¦¸.cm max. |
|
| |
| Download |
|
| |
| |
| |
| |
|