| 10/20kV heat shrinkable
joints |
Technical Data
| Item No. |
Property |
Test condition and Requirement |
Results |
1 |
AC withstand for 1 min.(dry withstand, for indoor termination) |
No breakdown and flashover shall occur at 105kV, 1min |
No breakdown and flashover occurred on the combi.sample |
2 |
Partial discharge |
39kV, ¡Ü10PC |
39kV, ¡Ü10PC |
3 |
Load cycle |
Heating for 5h, cooling for 3h. Conductor's temperature
is 95¡æ, 3 cycles |
Conductor's temperature is 95¡æ. Results refer to the
following test |
4 |
Impulse voltage withstand 1.2/50us¡À10times |
10 positiVe and 10 negative impulses at 250kV, flashover
1 time is allowed but not including total testing times |
No breakdown of the combi.sample occurred at 250kV |
5 |
DC voltage withstand negative 15 min. |
No breakdown and flashover shall occur at 156kV |
No breakdown and flashover occurred on the combi.sample |
6 |
AC voltage withstand, 4h |
No breakdown and flashover shall occur at 104kV, 4h |
No breakdown and flashover occurred on the combi.sample |
7 |
Oil-seal up test
(Only for Paper insulated cables) |
Heating for 24h, cooling for 24h. Conductor's temperature
is 65¡æ, oil pressure: 100MPA |
No leaking, no seeping |
|